MX8000 Installation and Operation Guide
5–30
Table 5–11: Line Device Menu Options (cont’d)
Select
Device
Type
Line
Device
Menu
Choice Choice Choice Choice Default Comments
Inter-digit
Tm (ms)
0 or 1 ms to 2
Sec.
0
This feature selects
the time period
between data blocks.
See page 5–41 for
more information.
Ack on
Even Round
Yes or No No
Select this option if the
1400 or 2300 Hz
format requires an Ack
tone on even rounds.
Pulse
Format
(cont’d)
Partially
Extended
Yes or No Yes
Select this option if
you have multiple
extended data blocks
for 3/ 1 or 4/1 formats.
Y (Yes)
Direct
No (No)
✔
Y = dedicated or direct
connect phone line.
N = used for standard
phone lines. See page
5–42 for more
information.
Number of
Rings
0-255 002 If caller ID is turned on
(see Section 5.5.2.5),
rings should be set to
2.
It is recommended
that the number of
rings is not set to a
value greater than 5.
Country
Country USA Select country from
listing.
Threshold
1-15 in 2.75
VDC steps
08 (22.0VDC) See page 5–43 for
more information.
Line
Options
Sample
Time
00-99
seconds
08 (8
seconds)
See page 5–43 for
more information.
Not Used
✔
Common
See page 5–44 for
more information.
Must not be used in
UL installations.
Listen Mode
PBX PBX String
edit
See page 5–44 for
more information.
Timeout
0-255 0 See page 5–45 for
more information.
Add Account None
Edit Account
Listen In
Listen In
account edit
Clear Account
See page 5–45 for
more information.
Y (Yes)
MX8000–
LC3
3 Line
(cont’d)
Edit Line
(cont’d)
Line #
(cont’d)
Misc. Line
Options
Echo
Suppress
N (No)
✔
Outputs a 2 second
2025Hz tone to disable
echo suppression
equipment that may
interfere with modem
formats.