Section 5 – Programming
5–43
To Change Country:
The “Country” field selects the country of your choice.
1. Follow the procedures in Section 5.5.2.
2. Press
3
for Line Options menu.
3. Press
until the display flashes on the Country field.
4. Press the or button to change the Country.
5. When the desired selection is flashing press
ENTER
MENU
or .
To Change the Ring Threshold Voltage:
The “Threshold” field controls the phone line low voltage/Line Fault threshold level. If the voltage on the
phone line connected to the line card drops below this set threshold level for that Device, the receiver will
indicate a Line Fault on that phone line.
1. Follow the procedures in Section 5.5.2.
2. Press
3
for Line Options menu.
3. Press
until the display flashes on the Thresh field.
4. Enter the desired value from the keypad or press the or button to change the Line fault
threshold level. Values range from 1 to 15 volts in 2.75 VDC increments (1=2.75VDC, 2=5.5VDC,
3=8.25VDC and so on).
5. When the desired line fault threshold is flashing press
ENTER
MENU
or .
To Change the Phone Line Sample Rate:
The sample field controls how often the receiver will sample the phone line to verify that it is above the set
threshold level of that line card. This is how often the receiver verifies the integrity of the phone line.
1. Follow the procedures in Section 5.5.2.
2. Press
3
for Line Options menu.
3. Press
until the display flashes on the Sample field.
4. Enter the desired value from the keypad or press the or button to change the line sample
rate. Values range from 00 to 90 in 1 second increments (0=Line monitor disabled, 1=1 second, 2=2
seconds, 3=3 seconds and so on). The receiver will make two to three samples before generating a trouble
condition on a faulty line.
5. When the desired sample time is flashing press
ENTER
MENU
or .
6. Press
to exit this menu.

Table of Contents