Table 25 HP UPS models and capacities
Capacity (in watts)UPS Model
1340R1500
2700R3000
4500R5500
12000R12000
Table 26 UPS operating time limits
Minutes of operation
Load (percent)
With 2 ERMsWith 1 ERMWith standby battery
R1500
49235100
6332680
161571350
2901463420
R3000
205100
306.580
451250
1204020
R5500
46247100
6031980
106611950
3031695920
R12000
18115100
2415780
41281450
101694320
Shock and vibration specifications
Table 27 (page 198) lists the product operating shock and vibration specifications. This information
applies to products weighing 45 Kg (100 lbs) or less.
NOTE: HP EVA products are designed and tested to withstand the operational shock and vibration
limits specified in Table 27 (page 198). Transmission of site vibrations through non-HP racks
exceeding these limits could cause operational failures of the system components.
Shock and vibration specifications 197