Tab Parameter Description
Smart diagnosis
function
Enable: If there is an intelligent
temperature control monitoring
board, this function is enabled to
start refrigerant status detection.
Disable: The smart diagnosis
function is disabled.
Conditions for starting refrigerant
status detection:
No low temperature component is
congured.
Altitude: ≤ 2000 m
7.5 m ≤ equivalent pipe length of
the one-way pipe ≤ 100 m
–8 m ≤ vertical distance between
the indoor and outdoor units ≤ +30
m
5°C ≤ outdoor ambient temperature
≤ 40.5°C
Require password to
start or shutdown
onsite
No: No password is required for
startup or shutdown.
Yes: A password is required for
startup and shutdown.
Altitude Set this parameter based on the actual
altitude.
Liquid pipe length Set this parameter after Smart
diagnosis function is set to Enable.
Specify the length of the liquid pipe
between the indoor and outdoor units
of a smart cooling product.
Height dierence
between indoor and
outdoor units
Set this parameter after Smart
diagnosis function is set to Enable.
Specify the height dierence between
the indoor and outdoor units of a
smart cooling product.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 158

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000-S and is the answer not in the manual?

Huawei FusionModule2000-S Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000-S
CategoryStorage
LanguageEnglish

Related product manuals