Tab Parameter Description
Heating function Enable: The device starts
humidifying when the ambient
temperature is lower than the
temperature setpoint by a certain
range.
Enabled when active power supply
is working: The device starts
heating only when the active power
supply is used and the ambient
temperature is lower than the
temperature setpoint by a certain
range. (The electric heater is an
auxiliary function. By default, it is
enabled when the active power
supply is used and is disabled when
the standby power supply is used.)
Disable: The heating function is
disabled.
Heating mode This parameter can be set to
Dehumidifying heating, Low-
temperature heating, or
Dehumidication & Low
temperature heating.
Dehumidifying heating: When the
dehumidifying function is enabled,
the electric heater is started to
supplement the cooling capacity to
achieve
dehumidication at
constant temperature.
Low-temperature heating: The
heating function is enabled when
the current temperature is lower
than the temperature setpoint by a
certain value.
Dehumidication & Low
temperature heating: Both
functions are available.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 159

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000-S and is the answer not in the manual?

Huawei FusionModule2000-S Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000-S
CategoryStorage
LanguageEnglish

Related product manuals