Step 6 Congure NAT on the IVS1800.
(1) Congure the MU:
1. Choose Maintenance > Unied Conguration, set Module Name to MU,
and click Search.
2. Click Edit in the record where the value of Parameter Name is MUNNatIP,
set the external IP address of the IVS1800, and click Save.
Figure 5-72 Setting the external IP address of the MU
3. Click Edit in the row where the value of Parameter Name is
NatRtspServerPort, and set the NAT port number of the MU. Ensure that the
setting is the same as the NAT mapped port number
congured on the
rewall. Click Save.
If no external IP address is mapped, retain the default value of NatRtspServerPort.
(2) Congure the OMU:
1. Set Module Name to OMU and click Search.
2. Click Edit in the row where the value of Parameter Name is OMUNNatIP
and set Value to the MUNNatIP address of the MU. Click Save.
Figure 5-73 Setting the external IP address of the OMU
(3) Congure the SMU:
1. Set Module Name to SMU and click Search.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 237