Maintenance
Area
Maintenance
Item
Operation Expected Result Troubleshootin
g
Cleanliness - Wipe the cabinet
surface using a
white paper and
the paper does
not turn black.
Remove the
dust, especially
from the air
lter on the
front door, or
replace the air
lter.
Parameter
conguration
- The
conguration of
the output
voltage grade,
frequency,
number of
batteries, and
battery capacity
meets
requirements.
Reset the
parameters.
Power cables and
terminals
(between the UPS
and the power
distribution
subrack)
- The insulation
layer of cables is
intact and
terminals are
free from
noticeable
sparks.
Replace
damaged
cables.
Secure
output
terminals.
Lithium battery Battery
management
alarm
- No battery
management
alarm is
generated.
Identify the
cause of an
alarm based on
the alarm
information.
FusionModule500 Smart Mini Data Center
User Manual 6 O&M