EasyManua.ls Logo

Huawei FusionModule500

Huawei FusionModule500
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
Area
Maintenance
Item
Operation Expected Result Troubleshootin
g
Battery
appearance
- 1. The surface is
clean and tidy
without
stains.
2. The battery
terminals are
intact.
3. Batteries are
free from
damage and
cracks.
4. Batteries are
free from acid
leakage.
5. Batteries are
not deformed
or bulged.
If the battery
appearance is
abnormal,
contact Huawei
technical
support.
Battery operating
temperature
- 1. Battery
operating
temperature:
0–45°C
(charging); –
20°C to +45°C
(discharging)
2. Battery
charge and
discharge
conditions
meet the
requirements
specied in
the battery
specications.
1. Identify the
cause of an
abnormal
battery
operating
temperature.
2. If the fault
persists,
contact
Huawei
technical
support.
Battery
management
parameter settings
- Check that the
settings of
battery
management
parameters meet
the requirements
in the user
manual.
Set parameters
correctly.
FusionModule500 Smart Mini Data Center
User Manual 6 O&M
Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 242

Table of Contents

Other manuals for Huawei FusionModule500

Related product manuals