Parameter Smart Cooling Product No.
1 2
Number of air conditioners
in this group
2 -
Number of running air
conditioners in this group
2 -
Rotation Enable -
Rotation period The parameter can be set by the
day ranging from one day to 30
days as required.
-
Rotation time The parameter can be set by the
hour ranging from midnight to
23:00 as required.
-
Requirement control Competitive running avoidance -
Table 5-2 Setting teamwork control parameters for three smart cooling products
Parameter
Smart Cooling Product No.
1 2 3
Teamwork
function
Enable Enable Enable
Teamwork
group no.
1 1 1
Air conditioner
address
1 2 3
Number of air
conditioners in
this group
3 - -
Number of
running air
conditioners in
this group
3 - -
Rotation Enable - -
Rotation period The parameter can be set by
the day ranging from one
day to 30 days as required.
- -
FusionModule800 Smart Small Data Center
User Manual 5 Power-On Commissioning
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 260

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals