Step 14 Choose Controls > Control Information, set Diagnostic mode to Exit, and click
Submit.
----End
6.4.3.2.4 Replacing a High Pressure Sensor
Prerequisites
● A high pressure sensor needs to be replaced.
● A spare high pressure sensor of the same model is available and functional.
Context
● Tools: Phillips screwdriver, refrigerant retrieval device (required based on local
conditions), nitrogen injection and pressure preservation tool, vacuumization
tool, refrigerant injection tool, adjustable wrench, sealant.
● Preparation: Power
o the outdoor unit.
● Figure 6-22, Figure 6-23, or Figure 6-24 shows the position of the high
pressure sensor.
Procedure
Step 1 Shut down the smart cooling product over the EMS.
● Method 1: Log in to the ECC800-Pro mobile phone or pad app as admin.
a. Choose Home.
b. Tap the cabinet that houses the smart cooling product in the micro-
module view.
c. Tap the smart cooling product to be set in the cabinet layout diagram.
d. Choose Real-time Data > OFF.
● Method 2: Log in to the ECC800-Pro WebUI as admin. Choose Monitoring >
Cooling > NetCol5000-A1 > Controls > Control Information, choose
Startup/Shutdown control > OFF, and then click Submit.
1 in NetCol5000-A1 is variable and subject to changes with the smart cooling product
connection sequence. The displayed value prevails.
Step 2 Disconnect the power supplies from the smart cooling product control unit and
the outdoor unit after the smart cooling product shuts down over the EMS.
Step 3 Open the top cover and right rear panel.
Step 4 Cut the cable ties on the high pressure sensor cable using diagonal pliers and take
out the high pressure sensor cable from the electric control box.
Step 5 Reclaim all the refrigerant from the system using a refrigerant retrieval device to
ensure that there is no pressure inside the system.
Discharge the refrigerant if the local laws and regulations allow.
FusionModule800 Smart Small Data Center
User Manual 6 O&M