B Equipment Derating Coecients
The coecients listed in the Table B-1 are based on the dry air density being 1.225 kg/m
3
(sea level +15ºC).
Table B-1 Derating coecients of the UPS2000-G
Altitude (Unit: m)
Derating Coecients
1000 1.0
1500 0.95
2000 0.91
2500 0.86
3000 0.82
3500 0.78
4000 0.74
4500 0.7
5000 0.67
FusionModule800 Smart Small Data Center
User Manual B Equipment Derating Coecients
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 493