EasyManuals Logo
Home>Huawei>Storage>FusionModule800

Huawei FusionModule800 User Manual

Huawei FusionModule800
508 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #454 background imageLoading...
Page #454 background image
there is no alarm, the outdoor fan is functional. Set Outdoor fan manual control
to 0% and click Submit.
Step 13 Choose Controls > Control Information, set Diagnostic mode to Exit, and click
Submit.
Step 14 Clear up the outdoor fan total runtime.
Method 1: Log in to the ECC800-Pro mobile phone or pad app as user admin.
a. Choose Home.
b. Tap the cabinet that houses the smart cooling product in the micro-
module view.
c. Tap the smart cooling product to be set in the cabinet layout diagram.
d. Choose Real-time Data > Perf Maint, and clear up the outdoor fan total
runtime.
Method 2: Log in to the ECC800-Pro WebUI as user admin. Choose
Monitoring > Cooling > NetCol5000-A1 > Controls > Performance
Maintenance Control, and clear up the outdoor fan total runtime.
----End
6.4.3.2.2 Replacing a Compressor
Prerequisites
Tools: diagonal pliers or scissors, Phillips screwdriver, 8 mm and 13 mm socket
wrenches, welding tool, refrigerant retrieval device (required based on local
conditions), nitrogen injection and pressure preservation tool, vacuumization
tool, refrigerant injection tool, protective gloves.
A compressor needs to be replaced.
A spare compressor of the same model is available and functional.
Context
Before replacing the compressor, disconnect the power supply and discharge
refrigerant from the system.
After the replacement, perform the leakage test with nitrogen, then
vacuumize again and charge refrigerant.
Reclaim or dispose of the refrigerant in accordance with the local laws and
regulations.
Remove the left front panel and left rear panel from the outdoor unit when
replacing the compressor.
Procedure
Step 1 Shut down the smart cooling product over the EMS.
Method 1: Log in to the ECC800-Pro mobile phone or pad app as user admin.
a. Choose Home.
b. Tap the cabinet that houses the smart cooling product in the micro-
module view.
FusionModule800 Smart Small Data Center
User Manual 6 O&M
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 442

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals