Maintenance Item Operation Expected Result Troubleshooting
Smart cooling product Monitoring unit Export smart cooling
product logs, alarms,
temperature, humidity,
the operating status of
the compressor, fan,
electric heater, wet
lm humidier, and
water pump, and time
from the management
system. View the
historical alarms
generated in this
quarter and select the
most common
ve
ones. (If no
management system
is available, skip this
item.)
Rectify the fault or
contact Huawei
technical support.
Electric control box
components
Check that all fuses
work properly.
Replace abnormal
fuses.
Check that the cable
connection is secure
and correct.
Secure loose cables.
Check that the
electrical components
and control
components of the
indoor unit are free of
dust.
(Perform the
operation with the
power o.) Use a
brush or compressed
dry air to remove dust
from electrical
components, control
components, and
voltage detection
boards.
Check that the
electrical components,
control components,
SPDs, and voltage
detection boards of
the outdoor unit are
free of dust.
Check that the
surfaces of the control
board, SPDs, and
voltage detection
boards are not aged.
Replace the abnormal
board.
FusionModule800 Smart Small Data Center
User Manual 6 O&M
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 365

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals