Component Alarm Name Alarm
Severit
y
Possible Cause Measures
BCB Tripping Critical The battery has
discharged to the
end-of-discharge
(EOD) threshold.
The battery circuit
breaker (BCB) box is
manually
disconnected.
There is a security
risk in the battery
loop.
Identify the alarm
cause, rectify the fault,
and switch on the BCB
box.
Single Batt.
terminal o
Critical A battery terminal
screw is not
tightened.
The battery terminal
is not properly
connected to the
connector.
Check that battery
terminal screws are
tightened.
Check that battery
terminals are
properly connected
to connectors.
Single Batt.
Exception
Critical The battery shell is
broken, resulting in
electrolyte and
electricity leakage.
The battery loop
cable is broken and
short-circuited to the
ground, resulting in
electricity leakage.
Check whether the
appearances of
abnormal batteries
are intact, and
replace abnormal
batteries.
Check whether
battery loop cables
are deteriorated or
broken, and replace
faulty cables.
Smart
cooling
product
Power loss Warnin
g
The supply power is cut
o.
Check the power supply
cables.
FusionModule800 Smart Small Data Center
User Manual 6 O&M
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 377

Table of Contents

Other manuals for Huawei FusionModule800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule800 and is the answer not in the manual?

Huawei FusionModule800 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule800
CategoryStorage
LanguageEnglish

Related product manuals