Component Alarm Name Alarm
Severit
y
Possible Cause Measures
Full water Critical 1. The low liquid level
sensor is faulty.
2. The condensate
water pump is faulty.
3. The drainpipe is
blocked.
4. The drainage
lter is
blocked.
1. Check the cables to
the low liquid level
sensor, clear the
obstacles, or replace
the low liquid level
sensor.
2. Check the cables to
the condensate
water pump, clear
the foreign matter in
the water pump, or
replace the pump.
3. Check that the
drainpipe is not
blocked or bent.
4. Clear the foreign
matter in the water
pan and
lter.
Drain abnormal Major 1. The high liquid level
sensor is faulty.
2. The condensate
water pump is faulty.
3. The drainpipe is
blocked.
4. The drainage
lter is
blocked.
1. Check the cables to
the high liquid level
sensor, clear the
obstacles, or replace
the high liquid level
sensor.
2. Check the cables to
the condensate
water pump, clear
the foreign matter in
the water pump, or
replace the pump.
3. Check that the
drainpipe is not
blocked or bent.
4. Clear the foreign
matter in the water
pan and
lter.
FusionModule800 Smart Small Data Center
User Manual 6 O&M
Issue 01 (2021-02-05) Copyright © Huawei Technologies Co., Ltd. 393