EasyManua.ls Logo

Huawei NetCol5000-C - Replacing a Condensate Pump

Huawei NetCol5000-C
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NetCol5000-C Chilled Water-Cooled In-Row Precision
Air Conditioner
User Manual
6 System Operation and Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
118
6.5.4 Replacing a Condensate Pump
The condensate pump stops drain water.
Prerequisites
The condensate pump needs to be replaced.
A spare and functional condensate pump valve is available.
Context
Recommended tool: Phillips screwdriver
Preparations: maintain from the rear door, and power off the condensate pump.
Procedure
Step 1 Remove the rear door and air filters.
Step 2 Disconnect all circuit breakers.
Step 3 Remove bolts on the condensate pump using a Phillips screwdriver, as shown in Figure 6-3.
Step 4 Remove the condensate drainpipes and control cables.
Step 5 Remove the screws fastening the condensate pump using a Phillips screwdriver and remove
the condensate pump, as shown in Figure 6-4
Step 6 Install a new condensate pump.
Step 7 Install the rear door and air filters.
Step 8 Tap Maint > Performance Maint on the home screen to enter the performance maintenance
screen, and clear accumulated running time of the condensate pump.