NetCol5000-C Chilled Water-Cooled In-Row Precision
Air Conditioner
User Manual
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2.6 Environment requirements
Table 2-2 describes the environment requirements for the NetCol5000-C.
Table 2-2 Environment requirements
NetCol5000-C030H2A2010020E0
Class A environment in data centers
Less than 1000 m. If the altitude exceeds 1000 m, the cooling
capacity decreases by 7% to 9% for every additional 1000 m.
Filter need to be installed on the inlet pipe, PH value of chilled
water is 7.0 ~ 9.0
Maximum water
temperature
1:When the ambient temperature is below 0 ° C, the NetCol5000-C need to increase certain
concentration of ethylene glycol solution, specifically refer to Glycol Correction Coefficient Curves
Glycol Correction Coefficient Curves.
2.7 Technical Specifications
Table 2-3 lists the technical specifications of the NetCol5000-C.
Table 2-3 Technical specifications of the NetCol5000-C030H2A2010020E0
Chilled water-cooled in-row precision air conditioner
200 V to 240 V 1 Ph 50/60 Hz