NetCol5000-C Chilled Water-Cooled In-Row Precision
Air Conditioner
User Manual
2 Product Description
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6
Physical Ports
Figure 2-4 Bottom and top views of the NetCol5000-C
1. Bottom outlet for the power and PE
cables
2. Bottom outlet for the signal cable and forcible
drainpipe
3. Bottom water outlet pipe
4. Condensate drainpipe port
5. Bottom water inlet pipe
6. Reserved hole for humidifier pipe
7. Top water outlet pipe
8. Top water inlet pipe
9. Top outlet for power line and PE
line
10. Top outlet for the signal cable and forcible
drainpipe
Table 2-1 lists the diameter of pipes and cables requirements.
Table 2-1 The diameter of pipes and cables
Content
Specification
Water inlet and outlet pipe
DN25 (Recommended diameter, prepare it by yourself)
Forcible drainpipes
Standard configuration: Φ=4 mm (OD Φ=7 mm), length =
5 m
Condensate Drainpipes
Standard configuration: Φ=10 mm (OD Φ=14 mm),
length = 2 m
Machine power supply core
2 × 2.5 mm
2
(Recommended diameter, prepare it by
yourself)
PE line (Outside the cabinet)
≥ 6 mm
2
(Recommended diameter, prepare it by yourself)