Figure 4-27 System Settings screen 3
NO TE
If lead-acid batteries are used, you can set Batt. temp. sensor [B_TEMP].
Item Description Default Value Value Range
Requisite
modules
Set this parameter based on
the system capacity.
- -
Redundant
modules
Set this parameter based on
load capacity and
redundancy requirements.
0 -
Working
mode
UPS working mode Normal mode Normal mode,
ECO, Self-load
mode,
Converter
mode
ECO voltage
range
In ECO mode, when the
dierence between the
bypass voltage and the rated
voltage is greater than the
specied value, the system
determines that the ECO
voltage is abnormal and
transfers to inverter mode.
±5% ±5%, ±6%,
±7%, ±8%,
±9%, ±10%
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 4 LCD Interface
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 99