Item Description Default Value Value Range
BSC mode Set this parameter to
Standard BSC mode for a
dual-bus system.
After setting this
parameter to Standard
BSC mode, you need to
set the two UPS systems
in the dual-bus system to
BSC master system and
BSC slave system
respectively in BSC
master/slave system.
(The two UPS systems
cannot be BSC master
systems or BSC slave
systems at the same time.
If you need to change the
settings in the future,
perform operations under
the guidance of
maintenance engineers.)
NOTE
Ensure that the BSC signal cable
between the BSC master and
slave systems is properly
connected and that BSC-related
hardware is properly installed.
Non-BSC
Non-BSC,
Standard BSC
mode
Altitude(m) Set this parameter based on
the altitude of the place
where the rack is used.
≤ 1000 ≤ 1000, 1000–
2000, 2000–
3000, 3000–
4000, 4000–
5000
Top outlet fan Enable this parameter if a
top outlet fan is congured.
Then the fan running status
can be checked.
Disable Disable,
Enable
Air lter
maintenance
period(d)
Species the rack air lter
maintenance interval. If you
set this parameter to 0, there
is no reminder.
0 0–365
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 4 LCD Interface
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 100