Battery Maint.
NO TICE
Perform battery maintenance when no alarm is generated on the UPS.
Otherwise, power output may fail.
A proportion of battery energy discharges during battery maintenance. This
reduces the discharge time before the next charge.
Do not perform battery maintenance when a generator is connected.
Battery maintenance items include Forced Equalized Charging, Shallow Dis.
Test, and Capacity Test.
Figure 4-43 Battery Maint. (lead-acid battery)
Figure 4-44 Battery Maint. (lithium battery)
Item
Description
Forced Equalized Charging This item allows you to perform equalized
charging on batteries forcibly.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 4 LCD Interface
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 120