EMC Test Item Standard
Voltage dips and short interruptions
(220 V AC)
IEC 61000-4-11
Table 9-6 Mains input electrical
specications
Item Specications
Input system Three-phase four-wire + PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input voltage range 80–280 V AC (phase voltage)
30–40°C environment: not derated when the
voltage range is 187–280 V; linearly derated to 40%
load when the voltage range is 187–80 V
0–30°C environment: not derated when the voltage
range is 176–280 V; linearly derated to 40% load
when the voltage range is 176–80 V
Input frequency range 40–70 Hz
Rated frequency 50/60 Hz
Input power factor > 0.99 (full load); > 0.98 (half load)
THDi ≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear
load; maximum: 5%)
Table 9-7 Bypass input electrical specications
Item
Specications
Power system Three-phase four-wire + PE
Rated voltage 380 V AC/400 V AC/415 V AC (line voltage)
Rated frequency 50/60 Hz
Frequency range 50/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6
Hz, ±2 Hz by default)
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 9 Technical Specications
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 168