Table 9-8 Battery specications
Item Specications
Battery voltage (lead-acid
battery)
360–528 V DC
● 12 V battery: 30–44 batteries, 40 batteries by
default; not derated when there are 36–44
batteries; power derated to 94% when there
are 34 batteries; power derated to 80% when
there are 32 or 30 batteries
● 2 V battery: 180–264 batteries, 240 batteries by
default; not derated when there are 216–264
batteries, power derated to 94% when there
are 204–214 batteries; power derated to 80%
when there are 180–202 batteries.
The number of batteries in the positive battery
string must be the same as that of batteries in
the negative battery string.
Battery management Intelligent battery management
Charger output power (6250 W±200 W) x N. The maximum charge
power of a power module is 6250 W±200 W
(maximum current limiting: 10 A). N indicates the
number of power modules in a rack.
Cold start When a mains outage occurs, batteries can start
the UPS and supply power to loads.
Charging voltage (lead-
acid battery)
● Equalized charge voltage:
2.3 V/cell to 2.4 V/cell, 2.35 V/cell by default
(30–42 batteries)
2.3 V/cell to 2.35 V/cell, 2.35 V/cell by default
(44 batteries)
● Float charge voltage:
2.23 V/cell to 2.3 V/cell, 2.25 V/cell by default
(30–44 batteries)
The UPS supports the SmartLi. For details about the parameters, see the
SmartLi
User Manual
.
Table 9-9 Output electrical specications
Item
Specications
Output mode Three-phase four-wire + PE
Voltage 380 V AC/400 V AC/415 V AC (line voltage)
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 9 Technical Specications
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 169