Alarm ID
(Alarm ID-
Cause ID)
Alarm
Name
Alarm
Severity
Causes Solution
0040-7 Rectier
abnormal
Critical The fans of
the power
module are
abnormal.
The
ventilation
channel of
the power
module is
obstructed.
1. Check whether the ventilation
channel of the power module is
blocked. If yes, rectify the fault to
restore the normal operation of the
fans.
2. Check whether the fans are
abnormal. Replace the power
module if the fans are faulty.
0043-1 Fan fault Critical The fans of
the power
module are
abnormal.
The fan
monitoring
cable for the
power
module is
abnormal.
Replace the faulty power module.
0043-2 The fan is faulty. Check the fan or replace the bypass
module.
0043-3 The fan is
faulty.
The fan
monitoring
cable is
faulty.
1. Replace the fan.
2. Check the fan monitoring cable.
0043-4
0047-1 Not ready Critical The ready
switch is OFF.
Turn on the ready switch.
0060-4 Inverter
abnormal
Critical A load short
circuit occurs.
A short
circuit occurs
inside the
module (this
fault seldom
occurs).
1. Check load cable connections.
2. If load cable connections are
normal, replace the power module.
0061-2 Inverter
alarm
Minor The I2C bus
is abnormal.
The E2PROM
is faulty.
1. Manually rectify the fault and
check whether the alarm is cleared.
2. If the alarm is generated again,
replace the power module.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) B Alarm List
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 177