Alarm ID
(Alarm ID-
Cause ID)
Alarm
Name
Alarm
Severity
Causes Solution
0061-7 Inverter
alarm
Minor The bypass
waveform is
abnormal.
If not all modules generate the
alarm, start the UPS, transfer it to
inverter mode, and replace the
modules that generate the alarm.
If all modules generate the alarm,
switch
o the bypass input circuit
breaker. After the inverter relay is
closed, switch on the bypass input
circuit breaker 10s later.
0085-1 EPO Critical The EPO button
is pressed.
Restore the EPO button status. Start
the UPS after the alarm is cleared.
0086-1 Max. BPM
transfer
times
Minor The system
frequently
transfers to
bypass mode
due to overload
timeout or load
impact.
Check the loads.
0087-1 Neighbor
transfer-to-
bypass
Warning The neighboring
UPS is abnormal
and transfers to
bypass mode.
Check the reason why the neighboring
UPS transfers to bypass mode.
0088-1 Rack address
conict
Critical The congured
rack address
conicts with
another one.
Check the rack address setting.
0089-1 Rack output
overload
Minor The loads are
excessive.
The rack
capacity
setting is not
appropriate.
If the loads are excessive, remove
some loads or expand the UPS
capacity.
Check that the congured rack
capacity meets requirements.
0090-1 Dry contact
board fault
Critical The I2C
communication
of the dry
contact card
MUE05A fails.
Replace the dry contact card MUE05A.
0090-2 The I2C
communication
of the dry
contact card
MUE06A fails.
Replace the dry contact card MUE06A.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) B Alarm List