Alarm ID
(Alarm ID-
Cause ID)
Alarm
Name
Alarm
Severity
Causes Solution
0095-1 Insu.
redundancy
Minor ● The loads are
excessive.
● The
congured
number of
redundant
modules is
incorrect.
1. Reduce the loads.
2. Decrease the congured number of
redundant modules.
0096-1 ECO volt.
abnormal
Minor ● The ECO
bypass
voltage or
frequency is
out of the
preset range.
● The ECO
bypass
voltage or
frequency
range is
incorrectly
set.
● The bypass
input
sequence is
reverse or
the neutral
wire is
disconnected.
1. Check the bypass input voltage and
frequency.
2. Check that the rated voltage, rated
frequency, ECO bypass voltage
range, and frequency range are
correctly set.
3. Check that the bypass cables and
circuit breakers are correctly
connected.
0098-1 Bypass
current not
shared
Minor ● The output
and input
circuit
breakers are
OFF.
● The length of
the bypass
input or
output power
cables is
incorrect.
● The bypass
SCR open-
circuits.
1. Check that the output circuit
breakers and bypass input circuit
breakers on each rack are ON.
2. Check that the length of the bypass
input or output power cables on
each rack are correct.
3. If the alarm persists, rectify any
bypass SCR open circuit.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) B Alarm List
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 179