Alarm ID
(Alarm ID-
Cause ID)
Alarm
Name
Alarm
Severity
Causes Solution
0564-1 Overload
timeout
Critical The loads are
excessive.
Derating
reduces the
rated system
power.
The module
is damaged.
1. Check that there is no overload.
2. Check that the module power is
not derated due to a fan fault.
3. If the alarm persists, replace the
power module.
0565-1 Transfer to
bypass mode
due to load
impact
Minor A large-
power RCD
load is
instantly
connected, or
the output
load short-
circuits.
The inverter
bridge short-
circuits.
1. Check the loads.
2. If the loads are normal, replace the
power module.
0566-1 Output
overload
Minor The loads are
excessive.
Derating
reduces the
rated system
power.
The module
is damaged.
1. Check that there is no overload.
2. Check that the module power is
not derated due to a fan fault.
3. If the alarm persists, replace the
power module.
0570-4 Bypass
module
abnormal
Critical The bypass
fan is
abnormal, or
the
ventilation
channel is
blocked.
The ambient
temperature
exceeds the
upper
threshold.
The loads are
excessive.
1. Check the bypass fan and
ventilation channel. If the fan is
faulty, replace it.
2. Check that the ambient
temperature does not exceed 40°C.
3. Check that there is no overload.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) B Alarm List
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 182