Alarm ID
(Alarm ID-
Cause ID)
Alarm
Name
Alarm
Severity
Causes Solution
0583-1 Inter-rack
par. cable
abnormal
Critical The inter-
rack parallel
CAN bus is
disconnected
or short-
circuits.
Only one
UPS works in
a parallel
system.
An ECM is
faulty.
1. Check the CAN bus.
2. Rectify the disconnection or short
circuit fault.
3. Replace the ECM.
0583-4 The inter-rack
industrial-
frequency
synchronization
cable is
disconnected.
Replace the inter-rack parallel cable.
0583-5 The inter-rack
carrier
synchronization
cable is
disconnected.
0583-6 The intra-
rack INVBYP
cable is
disconnected.
The parallel
CAN bus is
disconnected.
0584-2 Inter-rack
par. cable
alarm
Minor The inter-rack
parallel cable is
faulty.
Replace the inter-rack parallel cable.
0584-4 The inter-rack
industrial-
frequency
synchronization
cable is
disconnected.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) B Alarm List
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 183