UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Copyright © Huawei Technologies Co., Ltd.
154
Item
Description
Default Value
Value Range
Single/Parallel
Specifies whether the UPS works
in single mode or parallel mode.
Single
Single, Parallel
Requisite
modules
Matches the system capacity.
-
-
Redundant
modules
Set this parameter based on load
capacity and redundancy
requirements.
0
019
Working mode
UPS working mode
Normal mode
Normal mode,
ECO, Self-load
mode, Converter
mode
ECO voltage
range
In ECO mode, when the
difference between the bypass
voltage and the rated voltage is
greater than this value, the
system determines that the ECO
voltage is abnormal and transfers
to normal mode.
±5%
±5%, ±6%, ±7%,
±8%, ±9%,
±10%
BSC mode
Set this parameter to
Standard BSC for a dual-bus
system.
After setting this parameter to
Standard BSC, you need to
set the two UPS systems in
the dual-bus system to BSC
master system and BSC
slave system respectively in
the BSC master/slave system
setting. (The two UPS
systems cannot be BSC
master systems or BSC slave
systems at the same time. If
you need to change the
settings in the future, perform
operations under the guidance
of maintenance engineers.)
NOTE
Ensure that the BSC signal cable
between the BSC master and slave
systems is properly connected and
that BSC-related hardware is
properly installed.
Non-BSC
Non-BSC,
Standard BSC
Altitude (m)
Set this parameter based on the
altitude of the place where the
rack is used.
≤ 1000
≤ 1000,
10002000,
20003000,
30004000,
40005000