UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Copyright © Huawei Technologies Co., Ltd.
155
Item
Description
Default Value
Value Range
Top outlet fan
Enable this parameter if a top
outlet fan is configured. Then the
fan running status can be
checked.
Disable
Disable, Enable
Air filter
maintenance
period (d)
Specifies the rack air filter
maintenance interval. If it is set
to 0, there is no reminder.
0
0365
Intra-rack
power module
start delay (s)
These two parameters enable the
UPS to control the interval that
each rack (or module) transfers
from battery mode to normal
mode, which reduces the impact
on the generator or power grid. In
the case of battery undervoltage,
the system automatically shortens
the delay for transferring to
normal mode to 1/8 of the normal
delay to accelerate the transfer
and prevent battery
overdischarge. The start delay of
a module in a rack varies
depending on the rack number
and module number. #1 module
in rack 1 does not have a start
delay.
The default
value of this
parameter
depends on the
default number
of power
modules. The
default value is
2.0, 1.0, and 0.5
for 15, 610,
and 1020
power modules
respectively.
0.5120.0
Inter-rack
power module
start delay (s)
5
2120
NTC
The short-distance battery
temperature sensor monitors the
ambient temperature near
batteries, and ensures that
batteries work reliably and
securely.
Disable
Disable, Enable
BCB trips if
UPS stops
power supply
Indicates whether the BCB trips
when the system stops supplying
power and the output power is
off.
Enable
Disable, Enable