UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Copyright © Huawei Technologies Co., Ltd.
Input Settings
Figure 4-23 Input settings
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
D.G. power
limiting (kVA)
Set these two parameters to
control the valid input current
and limiting input current, which
prevents load impact and
facilitates better cooperation
between the UPS and the D.G.
Depends on the
actual model.
D.G. charger
power ratio (%)
Specifies whether to enable or
disable input current limiting to
protect generators.
Input cur.
limiting ratio
(%)
Limits the input current to protect
the D.G.