UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Copyright © Huawei Technologies Co., Ltd.
158
Item
Description
Default Value
Value Range
faulty, an interruption (less than
20 ms) occurs when the UPS
transfers from normal mode to
bypass mode. If Output freq.
track rate (Hz/s) is fast, the
inverter frequency is unstable.
Bypass Settings
Figure 4-25 Bypass settings
Item
Description
Default Value
Value Range
Maximum
bypass voltage
When the difference between the
bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
When the voltage level is 380 V,
the value range is +10%, +15%,
+20%, and +25%. The default
value is +15%.
When the voltage level is 400 V,
the value range is +10%, +15%,
and +20%. The default value is
+15%.
When the voltage level is 415 V,
the value range is +10% and
+15%. The default value is
+10%.
Minimum
bypass voltage
When the difference between the
bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
20%
10%, 15%,
20%, 30%,
40%, 50%,
60%
Bypass
frequency
When the difference between the
bypass input frequency and the
±2 Hz
±0.5 Hz to ±6