UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Copyright © Huawei Technologies Co., Ltd.
159
Item
Description
Default Value
Value Range
range (Hz)
rated frequency is greater than
the specified value, the system
determines that the bypass
frequency is abnormal, so the
bypass is unavailable.
Hz
Battery Settings
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following:
Battery string sharing is unavailable when Single/Parallel is set as Single.
Battery string sharing affects the actual charge current and the estimated discharge time.
An incorrect setting will cause a high or low charge current, which may damage the
batteries. An incorrect estimated discharge time may cause a data backup fault.
When you set parameters, ensure the following: Dis. cur. 0.1C EOD Dis. cur. 0.3C
EOD Dis. cur. 0.5C EOD Dis. cur. 1.0C EOD.
A cell consists of electrodes and electrolyte, which is the basic unit for the battery. Each
cell has a nominal voltage of 2 V. A battery is a module consisting of single or multiple
cells in a shell. Each battery has a nominal voltage of 2 V, 6 V, or 12 V.
Figure 4-26 Battery settings 1