UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Copyright © Huawei Technologies Co., Ltd.
163
Figure 4-31 Advanced Param.
Item
Description
Default Value
Value Range
Current source
Specifications of the Hall effect
sensor used to detect iBOX
current.
Hall sensor
200A
Hall sensor
200A, Hall
sensor 600A,
Hall sensor
1500A
Batt. abnormal
BCB trip
Specifies whether BCB trips
when batteries are abnormal.
Disable
Disable, Enable
Multi-Hall cur.
setting
Multi-Hall cur. setting is equal
to the number of Hall effect
sensors at the positive or negative
terminal of a battery string
(Multi-Hall cur. setting ≥ 1).
1