UPS5000-E-(50 kVA-300 kVA) 
User Manual (50 kVA Power Modules) 
 
Copyright © Huawei Technologies Co., Ltd. 
 
High ambient 
temperature 
alarm 
threshold (°C) 
An alarm is generated when the 
ambient temperature reaches or 
exceeds the threshold specified by 
this parameter. 
Low ambient 
temperature 
alarm 
threshold (°C) 
An alarm is generated when the 
ambient temperature is lower than the 
threshold specified by this parameter. 
Indicates whether to enable 
emergency power-off (EPO). EPO is 
performed only when this parameter 
is enabled and the EPO switch is 
triggered. 
When EPO detection is changed 
from Disable to Enable, check that 
the EPO cable is connected correctly. 
If this parameter is set to Enable, the 
UPS detects the bus capacitor 
lifespan. 
When customer loads are light, 
enable parallel hibernation to 
alternate modules in hibernation 
mode, which can prolong their 
service life and improve the system 
efficiency. 
Module cycle 
hiber. period 
(d) 
Indicates the rotation interval of 
modules in hibernation mode. The 
default value is 30, which means that 
the hibernating module is rotated 
every 30 days. 
Indicates whether ECO bypass is 
allowed to supply power in D.G. 
mode. When the D.G. is connected to 
the dry contact signal GEN: 
 
If this parameter is set to Enable, 
the system can enter ECO bypass 
mode when the D.G. supplies 
power to the bypass and the ECO 
function is enabled. 
 
If this parameter is set to Disable, 
the system is not allowed to enter 
ECO mode when the D.G. 
supplies power to the bypass. 
Enable or disable the memory check 
function. If this parameter is set to 
Enable, the control chip RAM