UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Copyright © Huawei Technologies Co., Ltd.
working status is checked regularly.
If this parameter is set to Disable,
regular check is disabled.
Collect
real-time site
waveform
If this parameter is set to Enable, one
waveform can be stored manually.
If this parameter is set to Enable, the
BCB will trip in case of EOD.
Table 4-13 Input settings
Input adaptability mode 1: It is
applicable to the normal power grid
and DGs, and DGs that are sensitive
to the output reactive component.
Input adaptability mode 2: It is
applicable to the normal power grid
and DGs, and input power sources
with high internal resistance.
Table 4-14 Output settings
Zero display
with no load
output
If this parameter is set to Enable,
the output current is displayed as
0 when no load is output. The
output load rate is displayed as
3%. When this parameter is set to
Disabled, the output current and
output load rate are not adjusted
to zero.
Calib. output
current if no
load
If this parameter is set to Enable,
the current at no load will be
calibrated once automatically.
This function can be used only
when the UPS carries no load.
Output
interruption
transfer time
(ms)
Set this parameter based on the
output interruption time
acceptable to loads.
0 ms, 40 ms, 60
ms, 80 ms, 100
ms, 120 ms