UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Copyright © Huawei Technologies Co., Ltd.
197
Item
Description
Default Value
Value Range
Float volt.
temp. comp.
coef.
(mV/°cell)
Calibration coefficient during
float voltage temperature
compensation.
3.3
0.06.0
Float Chg temp
comp center
C)
Indicates the reference
temperature during temperature
compensation of the float
charging voltage.
25
2030
Automatic
equalized
charging
If this parameter is set to Enable,
the UPS automatically changes
the battery management status to
equalized charge based on the
charge current and float charge
time.
Enable
Disable, Enable
Transfer-to-equ
alized charging
cur. coef. (C10)
The battery enters equalized
charge state when the battery
current exceeds this parameter
value.
0.05
0.020.08
SOC to start
equalized
charging (%)
If the SOC is lower than the
specified value, batteries start
equalized charging.
70
0100
Scheduled
equalized
charging
interval (d)
After batteries transfer from
equalized charging to float
charging, if the batteries do not
discharge, equalized charging
starts only after the float charging
time reaches Equalized
charging protection interval.
After equalized charging is
complete, scheduled equalized
charging starts when the
non-equalized charging time
exceeds Scheduled equalized
charging interval.
60
30180
Equalized
charging
protection
interval (d)
7
015
Forced
equalized
charging
protection time
(h)
When batteries are continuously
under float charging or
hibernation, enable forced
equalized charging. When the
forced equalized charging time
reaches the value of this
parameter, batteries
automatically transfer to float
charging mode.
18
1224
Max. batt. dis.
time (h)
Set the maximum battery
discharge time. When the
discharge time reaches this value,
the UPS powers off. The battery
discharge time can be set only to
24
048

Table of Contents

Other manuals for Huawei UPS5000-E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS5000-E Series and is the answer not in the manual?

Huawei UPS5000-E Series Specifications

General IconGeneral
BrandHuawei
ModelUPS5000-E Series
CategoryUPS
LanguageEnglish

Related product manuals