UPS5000-E-(50 kVA-300 kVA) 
User Manual (50 kVA Power Modules) 
 
Copyright © Huawei Technologies Co., Ltd. 
 
0 hours or a value only in the 
range of 16–48 hours. If the time 
is set to 0 hours, battery 
discharge protection is not 
implemented. 
If the mains is not functioning 
normally, the UPS will transfer 
to battery mode. When batteries 
reach the EOD threshold, the 
bypass is disabled, and EOD 
restart is Enable, the UPS will 
restart as soon as the mains 
resumes. 
If EOD restart is disabled, clear 
the alarm manually or enable the 
restart function for the UPS. 
If EOD restart is set to Enable, 
the UPS starts working after the 
time set for EOD restart delay 
when the input recovers from the 
power failure upon EOD. 
Undertemp. 
alarm thresh. 
(°C) 
Battery temperatures can be 
monitored in a timely manner. If 
a battery overtemperature alarm 
is detected, the charging current 
limit decreases to 0.03 CA. 
Battery charging stops if a 
battery overtemperature 
protection alarm (when the 
temperature reaches the high 
temperature threshold plus 3°C) 
is generated. 
Overtemp. 
alarm thresh. 
(°C) 
Single batt. 
float chg. 
voltage 
deviation alarm 
thres. (%) 
Single batt. float chg. voltage 
deviation alarm thres. (%) and 
Single batt. dis. voltage 
deviation alarm thres. (%) are 
used to check whether the cells in 
each battery string have the same 
charge voltage and discharge 
voltage. When a value exceeds 
the specified range, an alarm is 
generated. 
The calculation formula is 
(Charge/Discharge voltage – 
Average voltage)/Average 
voltage x 100%. 
Single batt. dis. 
voltage 
deviation alarm 
thres. (%) 
Batt. charging 
capacity 
mismatch 
After this function is enabled, an 
alarm is generated if the 
configured battery capacity