Alarm ID
(Alarm
ID-Cause
ID)
The bypass input
circuit breaker is
OFF.
The running status is displayed.
No further measures are required.
The maintenance
circuit breaker is
ON.
The running status is displayed.
No further measures are required.
The generator is
connected.
The running status is displayed.
No further measures are required.
Insufficient
redundant racks
The load is
excessive.
The configured
number of
redundant racks
is incorrect.
1. Reduce the load.
2. Decrease the configured
number of redundant racks.
The load is
excessive.
The configured
number of
redundant
modules is
incorrect.
1. Reduce the load.
2. Decrease the configured
number of redundant modules.
The ECO bypass
voltage or
frequency is out
of the preset
range.
The ECO bypass
voltage or
frequency range
is incorrectly set.
The bypass input
sequence is
reverse or the
neutral wire is
disconnected.
1. Check the bypass input voltage
and frequency.
2. Check that the rated voltage,
rated frequency, ECO bypass
voltage range, and frequency
range are correctly set.
3. Check that the bypass cables
and circuit breakers are
correctly connected.
Bypass current not
shared
The output and
input circuit
breakers are
OFF.
The length of the
bypass input or
output cables is
incorrect.
1. Check that the output and
bypass input circuit breakers
on each rack are ON.
2. Check that bypass input and
output power cables on each
rack meet the length
requirements.
3. Rectify any bypass SCR
open-circuit.