UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
B Alarm List
Copyright © Huawei Technologies Co., Ltd.
266
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
The bypass SCR
open-circuits.
0150-1
Inverter
asynchronous
Minor
The bypass
frequency
changes fast.
The output
frequency track
rate is incorrectly
set.
1. Check that the bypass output
frequency does not change
fast.
2. Check that the Output freq.
track rate is properly set.
0101-1
BSC signal
abnormal
Minor
The dual bus
connector is
loose.
Parameters are
set incorrectly.
1. Check the dual bus connector.
2. Check the parameter settings.
3. The master BSC system is not
supplying power.
0102-1
Maint. breaker
misoperation
Critical
The user operation is
incorrect.
1. Shut down the inverter and
then close the maintenance
circuit breaker.
2. After maintenance, open the
maintenance circuit breaker
and then start the inverter.
0380
In self-check
Warning
The inverter is in
self-check.
Wait until the inverter self-check
is complete.

Table of Contents

Other manuals for Huawei UPS5000-E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS5000-E Series and is the answer not in the manual?

Huawei UPS5000-E Series Specifications

General IconGeneral
BrandHuawei
ModelUPS5000-E Series
CategoryUPS
LanguageEnglish

Related product manuals