12
■International Standards Compliances■
SCON-CB/CGB/LC/LCG comply with the following international standards:
Refer to Overseas Standard Compliance Manual (ME0287) for more detailed information.
{: Applicable ×: Not Applicable
Controller RoHS Directive CE Marking UL
SCON-CB/LC/LCG ~ 750W
{ { {
~ 750W
{ { {
SCON-CGB
3000W ~
{ {
×
UL
1. Use Environment
• For use in pollution degree 2 environment
• Maximum surrounding air temperature rating, 40°C;
2. Solid State Motor Overload Protection
Solid state motor overload protection in the SCON controller is provided.
The overload protection works at 115% of the whole load current of the servomotor as the
criteria.
3. Short Circuit Current Rating (SCCR)
This product is to be used with a power supply of 5,000Arms or lower. The available maximum
voltage is as shown below:
200V system products: 240V AC
100V system products: 120V AC
4. Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection. Branch
circuit protection must be provided in accordance with the National Electric Code and any
additional local codes.
5. Risk of Electric Shock
Do not touch terminals within 10 minutes after disconnect the power. Risk of electric shock.