8. Parameter
283
8.2 Detail Explanation of Parameters
Caution: If parameters are changed, provide software reset or reconnect the power to
reflect the setting values.
The unit (deg) is for rotary actuator and lever type gripper. Pay attention that
it is displayed in mm in the teaching tools.
[1] Zone 1+, Zone 1- (Parameter No.1, No.2)
Zone 2+, Zone 2- (Parameter No.23, No.24)
No. Name Symbol Unit Input Range
Default factory
setting
1 Zone 1+ ZNM1
mm
(deg)
-9999.99 to
9999.99
Actual stroke on +
side
2 Zone 1- ZNL1
mm
(deg)
-9999.99 to
9999.99
Actual stroke on -
side
23 Zone 2+ ZNM2
mm
(deg)
-9999.99 to
9999.99
Actual stroke on +
side
24 Zone 2- ZNL2
mm
(deg)
-9999.99 to
9999.99
Actual stroke on -
side
These parameters are used set the zone in which zone signal (ZONE1 or ZONE2) turns ON in
a mode other than PIO patterns 1 to 3 (ZONE2 is valid only in the pulse-train control mode).
The minimum setting unit is 0.01mm (deg).
If a specific value is set to both zone setting + and zone setting -, the zone signal is not output.
A setting sample is shown below.
[Example of when line axis]
[Example of Rotary Actuator Index Mode]
Caution: The zone detection range would not output unless the value exceeds that of
the minimum resolution (actuator lead length / No. of Encoder Pluses).
Areas that the zone
signal is ON
315°
70°
315°
70°
0mm 30mm 70mm
ON
ON ON
100mm
Current Position
Zone signal output
Zone signal output
Set Value
Zone setting + : 70mm
Zone setting - : 30mm
Set Value
Zone setting + : 30mm
Zone setting - : 70mm