Goodrive300-01A-RT series integrated machine Fault handling and product maintenance
-95-
P19.14
State type
Possible cause
Solution
BIT2=1
Part 3 needs
maintenance
The running time of part 3
exceeds the time set by
P19.02.
Carry out maintenance after stop
BIT3=1
Part 4 needs
maintenance
The running time of part 4
exceeds the time set by
P19.03.
Carry out maintenance after stop
BIT4=1
Part 5 needs
maintenance
The running time of part 5
exceeds the time set by
P19.04.
Carry out maintenance after stop
BIT6=1
Auxiliary
temperature
signal fault
PT100 sensor is
disconnected.
Check whether the wiring of
PT100 is normal.
Temperature detection sensor
is abnormal.
Temperature detection input
circuit is abnormal.
BIT8=1
Auxiliary
temperature
pre-alarm
The actual temperature
detected by PT2 is larger
than the pre-alarm
temperature set by P18.19.
Temperature detection sensor
is abnormal.
Temperature detection input
circuit is abnormal, if not
calibrated.
The starting temperature of the
fan is set to a too high value.
The temperature of the fan is
set to a too high value.
Fan power is too small to
dissipate heat effectively.
BIT10=1
Auxiliary
temperature
alarm
The actual temperature
detected by PT2 is higher
than the alarm temperature
set by P18.20.
Temperature detection sensor
is abnormal.
Temperature detection input
circuit is abnormal, if not
calibrated.
The starting temperature of the
fan is set to a too high value.
The temperature of the fan is
set to a too high value.
The fan power is too small to
dissipate heat effectively.