1: Enable input phase loss software
protection
LED tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
LED hundreds:
0: Reserved
1: Reserved
LED thousands:
0: Disable phase sequence protection
1: Enable phase sequence protection
0x00–0x11
Ones: Current-limit action selection
0: Current-limit action is invalid
1: Current-limit action is always valid
Tens: Reserved
0x000–0x131
LED ones:
0: Motor overload/underload pre-alarm,
relative to the motor rated current
1: VFD overload/underload pre-alarm,
relative to the VFD rated current
LED tens:
0: The VFD keeps running after reporting an
overload/underload alarm.
1: The VFD keeps running after reporting an
underload alarm, but it stops running after
reporting an overload alarm.
2: The VFD keeps running after reporting an
overload alarm, but it stops running after