Goodrive300-01A-RT series integrated machine Function description
-59-
Function
code
Name
Description
Default
Modify
1: Enable input phase loss software
protection
LED tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
LED hundreds:
0: Reserved
1: Reserved
LED thousands:
0: Disable phase sequence protection
1: Enable phase sequence protection
P11.03
Overvoltage stall
protection
0: Disable
1: Enable
1
P11.04
Overvoltage stall
protection voltage
120150% (standard bus voltage) (380V)
140%
P11.05
Current limit selection
0x000x11
Ones: Current-limit action selection
0: Current-limit action is invalid
1: Current-limit action is always valid
Tens: Reserved
1
P11.06
Automatic current-limit
level
50.0200.0%
150.0%
P11.07
Frequency drop rate at
current limit
0.0050.00Hz/s
10.00Hz/s
P11.08
Pre-alarm selection for
VFD/motor
overload/underload
0x0000x131
LED ones:
0: Motor overload/underload pre-alarm,
relative to the motor rated current
1: VFD overload/underload pre-alarm,
relative to the VFD rated current
LED tens:
0: The VFD keeps running after reporting an
overload/underload alarm.
1: The VFD keeps running after reporting an
underload alarm, but it stops running after
reporting an overload alarm.
2: The VFD keeps running after reporting an
overload alarm, but it stops running after
0x000