Chapter 5 Parameters
72
P064 Torque limit selection
Range
Default
value
Unit Usage
03 0 ALL
Set torque limit mode:
0: internal torque limit;
1~2: reserved;
3: Torque limit comes from network
P065 Internal forward (CCW) torque limit
Range
Default
value
Unit Usage
0300 300 % ALL
Set the internal torque limit in the CCW direction of the motor.
At any time, this restriction is in effect.
If the setting value exceeds the maximum allowable system overload capacity, the actual
limit is the maximum allowable system overload capacity.
P066 Internal reversal (CW) torque limit
Range
Default
value
Unit Usage
-3000 -300 % ALL
Set the internal torque limit in the CW direction of the motor.
This restriction is in effect at all times.
If the value exceeds the maximum overload capacity allowed by the system, the actual
limit is the maximum overload capacity allowed by the system.
P070
Forward (CCW) torque overload
alarm level
Range
Default
value
Unit Usage
0300 300 % ALL
Set forward torque (CCW) overload value, which is a percentage of the rated torque.
When the positive torque of the motor exceeds P070 and the duration is longer than P072,
the driver will alarm with the alarm number of Err29 and the motor will stop running.
P071
Reverse (CW) torque overload alarm
level
Range
Default
value
Unit Usage
-3000 -300 % ALL
Set the reverse torque (CW) overload value, which is a percentage of the rated torque.
When the motor reverse rotation torque exceeds P071 and the duration is longer than
P072, the driver will alarm with the alarm number of Err29 and the motor will stop
running.
P072 Torque overload alarm detection time
Range
Default
value
Unit Usage
010000 0 10ms ALL
Refer to the description of parameters P070 and P071.