Chapter 5 Parameters
80
P131 Digital output DO2 function
Range
Default
value
Unit Usage
-2828 0 ALL
Digital output DO2 function planning, refer to parameter P130 description.
P132 Digital output DO3 function
Range
Default
value
Unit Usage
-2828 0 ALL
Digital output DO3 function planning, refer to parameter P130 description.
P133 Digital output DO4 function
Range
Default
value
Unit Usage
-2828 0 ALL
Digital output DO4 function planning, refer to parameter P130 description.
P134 Digital output DO5 function
Range
Default
value
Unit Usage
-2828 0 ALL
Digital output DO5 function planning, refer to parameter P130 description.
P149 Delay time of dynamic braking
Range
Default
value
Unit Usage
01000 0 ms ALL
Parameter meaning:
When the dynamic braking delay time is set to 0, the dynamic braking function is invalid.
P164 Delay time of dynamic braking
Range
Default
value
Unit Usage
01 0 ALL
When EMG (emergency shutdown) in DI is ON, the meaning of this parameter is:
0: Drive directly cut off the motor current, motor free stop;
1: the driver can keep status, control motor to 6085 h (Quick stop deceleration) defined
by the deceleration to stop.
P165 Motor static speed detection point
Range
Default
value
Unit Usage
01000 5 r/min ALL
Motor static detection, motor speed is lower than the parameter value is considered to be
static motor.
Used only for timing judgment of electromagnetic brakes.