5 - 6 VM600 MPS hardware manual (standard version) MAMPS-HW/E
Edition 17 - February 2018
Multi-channel processing functions
AMC8 / IOC8T CARD PAIR
5.4 Multi-channel processing functions
Four “multi-channel” processing functions are available. Each is able to process the following
functions on the 8 single channels:
Minimum of 2 to 8 values
Maximum of 2 to 8 values
Average of 2 to 8 values
Difference between two values.
5.5 Time-domain processing functions
These functions are somewhat analogous to the rectifier functions available for the
MPC4 / IOC4T card pair.
A time-domain processing function can be applied to a single channel or a “multi-channel”.
The following possibilities exist:
Direct output (bypass)
Average over a period of time
Maximum value over a period of time
Minimum value over a period of time.
The time period can be set under software control to a value between 0.1 and 10.0 seconds.
The output is updated at this rate.
5.6 Linearity compensation
The VM600 MPS software allows linearity compensation for thermocouples and RTD
devices.
For linear compensation, an offset and sensitivity value can be defined.
For non-linear compensation, a table of polynomial values can be entered or downloaded.
NOTE: Refer to the relevant manual for further information: VM600 MPS1 software
manual or VM600 MPS2 software manual.

Table of Contents

Other manuals for Meggitt VM600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Meggitt VM600 and is the answer not in the manual?

Meggitt VM600 Specifications

General IconGeneral
BrandMeggitt
ModelVM600
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals