EasyManua.ls Logo

Meggitt VM600 - Connection Diagram for Frequency Generator

Meggitt VM600
362 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VM600 MPS hardware manual (standard version) MAMPS-HW/E 9 - 19
Edition 17 - February 2018
Connecting vibration and pressure sensors
CONFIGURATION OF MPC4 / IOC4T CARDS
9.2.5 Connection diagram for frequency generator
Notes
1- Switch Sw1 is open to allow voltage-modulated signals to be processed.
The Signal Transmission Mode field has to be set to the Voltage option.
2- Switch Sw2 is set to position 1. This connects the IOC4T card's sensor power supply to
the PS terminal, though in fact this terminal is not used.
the Sensor Power Supply field can be set to any powered option (+27 VDC, 27 VDC,
+15 VDC or +6.16 mA) but should preferably be set to +6.16 mA.
Figure 9-13: Connection diagram
Sensor
power
supply
Frequency
generator