EasyManuals Logo

Meggitt VM600 Hardware Manual

Meggitt VM600
362 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #234 background imageLoading...
Page #234 background image
9 - 30 VM600 MPS hardware manual (standard version) MAMPS-HW/E
Edition 17 - February 2018
Configuring the four local relays on the IOC4T
CONFIGURATION OF MPC4 / IOC4T CARDS
9.4 Configuring the four local relays on the IOC4T
Connector J2 of the IOC4T card has terminals for the following four relay outputs:
RL1 – Pins 9 and 10 on connector J2
RL2 – Pins 11 and 12 on connector J2
RL3 – Pins 13 and 14 on connector J2
RL4 – Pins 15 and 16 on connector J2.
Specific alarms can be attributed to these relays using the VM600 MPSx software.
NOTE: Refer to the relevant manual for further information: VM600 MPS1 software
manual or VM600 MPS2 software manual.
Specific alarms (A+, D and so on) generated by an MPC4 card can be selected as control
signals for these local relays using the VM600 MPS software. The control signals are
generally low in the absence of an alarm, that is, in a “normal” state (which means that the
control signal is high-impedance), although there are exceptions to this rule as shown in
Table 9-4.
In the event of an alarm, the appropriate control signal changes state (which generally means
that the control signal is pulled low to ground).
Table 9-4: Normal state of “control signals” (in absence of alarm condition)
Parameter
Normal
state
Parameter
Normal
state
Common OK (Common OK alarm
level)
0 DSP Saturation Error 0
Individual OK 1 Status Latched (Error Log) 0
Common Alert (Common Alert
alarm level)
0 Input Signal Error 0
Individual Alert 0 Input Saturation Error 0
Common Danger (Common
Danger alarm level)
0 Common Mode Range Overflow 0
Individual Danger 0 Invalid Output 0
TM, DB, AR 0 Speed Out Of Limit 0
MPC Card Running 1 Track Lost 0
Common Monitoring Failure 0 Track Out Of Range 0
Processing Error 0 PGA Saturation Error 0
Key: 0 = control signal in low state, 1 = control signal in high state.

Table of Contents

Other manuals for Meggitt VM600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Meggitt VM600 and is the answer not in the manual?

Meggitt VM600 Specifications

General IconGeneral
BrandMeggitt
ModelVM600
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals