VM600 MPS hardware manual (standard version) MAMPS-HW/E 3 - 15
Edition 17 - February 2018
VM600 6U 19" rack backplane (ABE04x)
GENERAL SYSTEM DESCRIPTION
NOTE: The IOC8T card does not support the Raw Bus, so sharing an analog signal
between an AMC8 / IOC8T card pair and a condition monitoring card pair (such as
the CMC16 / IOC16T) requires that either:
• A DC output from the IOC8T is connected to a dynamic input channel of the
IOC16T using external cabling
• Modbus is used to communicate the analog values (which requires that a CPUM
card is also installed in the rack).